D4100 Voltage Output Modules

$350.00

The D4100 series analog output modules contain an isolated 12-bit digital to analog converter that is scaled to generate DC voltage signals commonly used in the process control, production test and motion control industries. Six voltage output ranges are available.  Simple commands are used to control the 12-bit digital to analog converter through either an RS-232 or RS-485 serial port.

The D4100 series modules include advanced features for improved system safety, including user-scalable input data values, a communications watchdog timer, user-programmable starting value, analog output slew-rate control and true analog output readback.

The communications watchdog timer, together with the user-programmable starting value, can be programmed to force the voltage output signal to a known “safe” condition in the event of a communications failure. Ensuring that control devices like valves will not remain open if a communications cable is severed.

The D4100 contains an 8-bit analog to digital converter for true readback of the voltage output signal.  While not a highly accurate measurement, the readback will provide assurance that the voltage output is working correctly. Use the readback to detect fault conditions, excessive load conditions, and wiring errors.

Three onboard digital inputs accept direct contact closures from switches or relays.  Making them ideal for monitoring on/off signals like cabinet door status or manually controlling the analog output at a remote module location.

Download Datasheet

Download Manual

The D4100 series modules can also be mounted on a DIN-Rail using the MK-1 mounting kit.

Additional Information

Dimensions 3.6 × 2.45 × 1.1 in
Specifications

• Voltage Output Ranges: +/-1V, +/-5V, +/-10V, 0-1V, 0-5V, 0-10V.
• Accuracy: 0.1% of full-scale range max
• 12-bit output resolution
• 1000 conversions per second
• Settling time: 300uS typical (1 mS max.)
• Span tempco: +/-50ppm/degree C max
• Voltage output drive: 5mA max
• Readback of Analog Output Signal
• Communications Watchdog Timer
• User-programmable Starting Value
• User-scalable input data values
• Readback of Analog Output Signal
• Three digital inputs

Communications

RS-232 Only, RS-485 Only