D7730 Modbus TCP/IP Ethernet Digital Input/Output Module

$295.00

The D7730 Digital Output Module contains seven digital input bits, eight digital output bits and communicates using the Modbus TCP Ethernet protocol.

The digital inputs have TTL switching levels, <1V=logic โ€œ0โ€ and >3.5Vdc=logic โ€1โ€.ย  The inputs can accept 0-30Vdc signals without damage. The digital inputs contain internal pull-up resistors for direct connection to contact closures, relays, and annunciators.

The digital outputs are open-collector transistors, can sink up to 100mA per bit and can be pulled up to 30Vdc without damage. A user-programmable Initial Value register specifies the On/Off state of each bit on power-up

A communications Watchdog Timer can be enabled to force the digital outputs to a known โ€œsafeโ€ condition in the event of a communications failure. ย The โ€œsafeโ€ state of each digital output bit is specified in the Initial Value register.

Download Data Sheet

Download Manual

The D7730 digital input module can be mounted on a DIN-Rail using the MK-1 mounting kit.

Out of stock

Additional Information

Dimensions 7.14 × 4 × 1.5 in
Features

โ€ข Seven Digital Inputs
โ€ข Eight Open-Collector Digital Output Module.
โ€ข RJ-45 10/100Mbps Ethernet Interface.
โ€ข Modbus TCP/IP Ethernet Protocol.
โ€ข IP Address, Static or DHCP (Default).
โ€ข 500Vrms Isolation.
โ€ข Seven discrete digital input bits.
โ€ข Eight discrete digital output bits.
โ€ข Requires +10V to +30Vdc unregulated supply, 10.W.
โ€ข Removable screw terminal plug connectors.
โ€ข CE marked.
โ€ข Internal pull up resistors on inputs for direct switch input
โ€ข Communications Watchdog Timer
โ€ข User Programmable Digital Output Initial Values

Software

The D7730 digital input/output modules are compatible with all commercial software programs and OPC servers that support the Modbus TCP/IP ethernet protocol. Commercials software programs from DreamReport, Wonderware, Indusoft, DAQFactory and DASYLab all support the Modbus TCP/IP ethernet protocol. OPC Servers from Kepware and MatrikonOPC support the Modbus TCP/IP ethernet protocol.

Applications

โ€ข Process monitoring and control
โ€ข Remote data logging to any host computer
โ€ข Product testing

Click outside to hide the comparison bar