Jewell DGL Series – AC Ammeters/Voltmeters

The moving coil, rectifier panel meters DGL 48/72/96/144 are housed in polycarbonate cases and are suitable for the measurement of AC currents and voltages. Moving coil rectifier instruments measure average values and are calibrated to indicate RMS values, assuming a sinusoidal waveform for frequencies from 40 to 10000 Hz (AC current – 40 to 1000 Hz and AC Voltage – 40 to 10000 Hz). These instruments offer several advantages in switchboards and generating set panels. A number of meters can be mounted in a panel cutout (mosaic mounting). The front glass, bezel, and dial can be easily replaced.

Additional information

Features

• Better Resolution
• Less VA burden
• Linear Scale
• Glass-filled polycarbonate housing (UL 94-V-0)
• Knife-edge pointer
• Easily replicable glass and bezel

Movement

Moving coil movement has pivots of very high hardness. Movement is suspended between spring-loaded sapphire jewels. Movement is properly shielded and critically damped by eddy currents induced in coil former.

Case Options

• Antiglare glass front fascia
• Red, yellow, blue, or white bezel color
• Front adjustable on-site red index pointer
• 0° to 180° position of use available on request

Dial Options

• Blank dial with initial and end values marked
• Number or letter markings
• Basic divisions without numbering
• Red or green markings or bands

Other Options

• Increased sensitivity to 4kohm/V for voltmeters 1 – 600V, and 10kohm/V for voltmeters 15 – 150V
• Resistance adjustment within ±1% at 23°C

Specifications

Mechanical

Case DetailsMolded square suitable for mounting in control switchgear panels and machinery consoles.
Case MaterialPolycarbonate, flame retardant, and drip-proof per UL 94-V-0
Front FasciaGlass
Color of BezelBlack
Position of UseVertical
Panel FixingMounting clamps
MountingStackable in a single cutout
Panel Thickness≤25mm
TerminalsVoltmeters & Ammeters <10A: Hexagon studs, M4 screws and wire clamps, E3 (DIN 46282).

Electrical

Measured QuantityAC voltage or current
Overload CapacityAcc to IS: 1248/IEC 51
Continuously1.2 times rated voltage/current
Short Duration2 times, 5 seconds maximum: 1 overload
10 times rated voltage, 0.5 seconds maximum: 9 overload
Enclosure Code (IEC 529)IP 52 - case cover
IP00 - terminals without back cover
IP20 - terminals with back cover
Insulation ClassGroup A according to VDE 0110
Insulation Category300 VCAT III
Rated Insulation Voltage660V
Proof Voltage2kV
Insulation Resistance<50MΩ at 500 Vdc

Scale & Pointer

ModelDGL48DGL72DGL96DGL144
Scale Length70mm106mm142mm230mm
Scale CharacteristicsLinear
Scale DivisionCoarse - Fine
Scale InterchangeabilityInterchangeable
PointerKnife edge
Pointer Deflection0-240°

Environmenal

Climatic SuitabilityClimate category II as per IS:1248, IEC 60051
Climatic class III according to VDE/VDI 3540
Operating Temperature-10° to +55°C
Storage Temperature-25° to +65°C
Relative Humidity≥75% annual average, non-condensing
Shock Resistance15gn for pulse duration 11ms
Vibration Resistance10-55-10 Hz for amplification 0.15mm (1.5g at 50Hz)
Pollution Degree2

Applicable Standards

IS 2419
DIN IEC 61554
Nominal case and cutout dimensions for indicating electrical instruments
IS 1248
DIN 43802
Scale and pointer for electrical measuring instruments.
IS 1248
DIN 43807
Connections and terminal markings for panel meters.
DIN 46200
DIN 46282
Terminal bolts/leads
IS 9249
DIN 40050
VDE 0110
VDE 0410
IEC 529/IEC 1010
Safety requirements and protective measures for electrical indicating instruments and their accessories.
IS 1248
IEC 51/DIN EN 60051
DIN 43701
IS 1248
IS 9000
VDE/VDI 3540
Performance specifications for direct acting indicating analog electrical measuring instruments and their accessories.
DIN 43718Front frames for indicating measuring instruments principle dimensions
UL 94-V-0UL combustibility class
DIN 43701Technical conditions of delivery for electrical instruments
IS 1248
IS 9000
VDE 0411
IEC 1010
Mechanical strength (free-fall test, vibration test)

European Compliances

2004/108/ECEMC directive
2006/95/ECLow voltage directive
Amendment 93/68/EECFor CE marking

Downloads